What would prevent a Control Expert (formerly Unity Pro) Quantum PLC from performing CCOTF successfully?
Issue:
What would prevent a Control Expert (formerly Unity Pro) Quantum PLC from performing CCOTF successfully?
Product Line:
Control Expert (formerly Unity Pro) Quantum PLC
Resolution:
- In order for CCOTF to perform successfully you need to enable the feature in the PLC configuration prior to initial download.
- The CRP and CRA interfaces must also be using a firmware version capable of performing CCOTF. You can check %SW98 and %SW99 to verify if these interfaces are CCOTF compliant.
If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.