What can cause InF6 (Internal Error 6) fault on ATV600 or ATV900 Series Process drives?
Issue:
Getting InF6 fault on Process drives.
Product Line:
ATV630, ATV930, ATV600, ATV900
Environment:
All
Cause:
NA
Resolution:
Unknown or Incompatible Option Board installed.
The compatibility of the option card(s) is monitored internally, if an unknown card is installed, INF6 error is triggered.
Probable causes:
The option module installed in the drive is not recognized.
The removable control terminal modules (if existing) are not present or not recognized.
The embedded Ethernet adapter is not recognized.
Remedies:
Verify the catalog number and compatibility of the option module.
Plug the removable control terminal modules after the drive has been switched off.
Getting InF6 fault on Process drives.
Product Line:
ATV630, ATV930, ATV600, ATV900
Environment:
All
Cause:
NA
Resolution:
Unknown or Incompatible Option Board installed.
The compatibility of the option card(s) is monitored internally, if an unknown card is installed, INF6 error is triggered.
Probable causes:
The option module installed in the drive is not recognized.
The removable control terminal modules (if existing) are not present or not recognized.
The embedded Ethernet adapter is not recognized.
Remedies:
Verify the catalog number and compatibility of the option module.
Plug the removable control terminal modules after the drive has been switched off.
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.