Issue:
How do we evaluate number of modifications in M580 HSBY?
Would every variable change or section change be taken account as 1 number of modifications.?
Product Line:
Modicon M580
Environment:
EcoStruxure Control Expert
Unity Pro
Resolution:
No.The number of modifications configured at Hot Standby tab of CPU is used to specify the maximum number of modifications allowed between Primary CPU & Standby CPU.
The number of modifications increase by 1 upon every build change (no matter how many variables or sections you had changed within the same time period)
How do we evaluate number of modifications in M580 HSBY?
Would every variable change or section change be taken account as 1 number of modifications.?
Product Line:
Modicon M580
Environment:
EcoStruxure Control Expert
Unity Pro
Resolution:
No.The number of modifications configured at Hot Standby tab of CPU is used to specify the maximum number of modifications allowed between Primary CPU & Standby CPU.
The number of modifications increase by 1 upon every build change (no matter how many variables or sections you had changed within the same time period)
Publikováno pro: Schneider Electric Česká republika

