Jak vám dnes můžeme pomoci?

What are possible causes for DB Unit Short Circuit Fault on ATV930 drive?

Issue:
Possible causes for DB Unit Short Circuit Fault on ATV930 drive

Product Line:
ATV930, Altivar 930

Environment:
All

Cause:
NA

Resolution:
The fault may occur if the DB Transistor is shorted. Perform a diode check across PA to PB to check if Transistor is shorted. Also, check BrA is set to Yes.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

Zjistěte více

Potřebujete pomoc?

Nástroj pro výběr produktů

Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.

Získejte nabídku

Poptejte se nás online a náš lokální specialista se s vámi spojí!

Kde nakoupit?

Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.

Centrum nápovědy

Zdroje podpory pro všechny své potřeby najdete na jednom místě.