How do I transfer programs from one ATV630/930 series drive to another with the VW3A1111 graphics keypad?
Issue:
Transfer programs from one ATV630/930 series drive to another with the VW3A1111 graphics keypad
Product Line:
Altivar 630/930
Environment:
All
Cause:
N/A
Resolution:
Please note:When transferring programming, the following must be the same for all drives involved:
To copy the drive's programming to the keypad:
From main menu, go into menu 7 'File management'
Enter menu 7.1 'Transfer config file'
Press OK to continue.
Disconnect the keypad from the drive and connect it to the drive to which you want to copy the programming.
Downloading from the keypad to the drive is similar:
From main menu, go into menu 7 'File management'
Enter menu 7.1 'Transfer config file'. In this menu choose 'Copy to the drive'
The drive will prompt you to choose which file you want to use so it is important to remember the name of the file you saved to prior.
Select the file you wish to use and press OK
Transfer programs from one ATV630/930 series drive to another with the VW3A1111 graphics keypad
Product Line:
Altivar 630/930
Environment:
All
Cause:
N/A
Resolution:
Please note:When transferring programming, the following must be the same for all drives involved:
- drives' part numbers
- firmware versions
- wiring setup
- option cards
- revision "rev" number
- IP rating
To copy the drive's programming to the keypad:
From main menu, go into menu 7 'File management'
Enter menu 7.1 'Transfer config file'
In this menu you have 2 options:
- 'Copy to the drive' (from the keypad)
- 'Copy from the drive' (to the keypad)
Press OK to continue.
Disconnect the keypad from the drive and connect it to the drive to which you want to copy the programming.
Downloading from the keypad to the drive is similar:
From main menu, go into menu 7 'File management'
Enter menu 7.1 'Transfer config file'. In this menu choose 'Copy to the drive'
The drive will prompt you to choose which file you want to use so it is important to remember the name of the file you saved to prior.
Select the file you wish to use and press OK
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.