TeSys T Motor Management Controller, Z1, Z2 terminals connection in case an External Ground current transformer is not used
Issue:
If an external ground current transformer is not being used, is it necessary to connect anything to the Z1 and Z2 terminals of the LTMR?
Product Line:
Tesys T LTMR product line.
Environment:
All situations where an external ground current transformer is not being used.
Cause:
Clarification of product characteristics.
Resolution:
If external ground current transformer is not used, then nothing should be connected to terminals Z1, Z2 of LTMR.
If an external ground current transformer is not being used, is it necessary to connect anything to the Z1 and Z2 terminals of the LTMR?
Product Line:
Tesys T LTMR product line.
Environment:
All situations where an external ground current transformer is not being used.
Cause:
Clarification of product characteristics.
Resolution:
If external ground current transformer is not used, then nothing should be connected to terminals Z1, Z2 of LTMR.