Video: Can I read a Float Value with a Read_Var SoMachine 4.3 ?

You will need to assign a variable to %MDx Location and Read at least 2 registers where the Float is located on your Remote Device. Move the Registers into %MWx*2 and %MWx*2+1.

See Attached project archive file for example. The following video demonstrates this procedure:

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.