Jak vám dnes můžeme pomoci?

How to Configure a Third Stage of Neutral Voltage Displacement Protection (59N) on a Powerlogic P3 protection relay

Issue

The device provides only two dedicated stages of neutral voltage displacement (59N), but the customer requires three stages.

Product

Powerlogic  P3 protection relay

Environment

Protection function configuration – Neutral Voltage Displacement (59N)

Cause

The standard protection package includes only two predefined 59N stages. Additional stages must be configured manually using programmable protection stages.

Resolution

To add a third 59N stage:

  1. Activate one of the eight programmable stages available in the device.
  2. Set the input coupling to Uo.
  3. Configure the threshold and settings in the same manner as one of the dedicated 59N stages.
  4. Save and apply the configuration.

This provides functionality equivalent to an additional 59N stage.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie