PME licenses are activated and displaying in Floating License Manager but Management Console states that software is not licensed
Issue
Occasionally, the licenses display correctly in Floating License Manager but when you open Management Console an error appears indicating that the software is not licensed. Additionally, the Management Console "About" box displays no licensed modules.
Product Line
PME Software
Environment
Management Console
Resolution
To prevent this error from appearing:
Occasionally, the licenses display correctly in Floating License Manager but when you open Management Console an error appears indicating that the software is not licensed. Additionally, the Management Console "About" box displays no licensed modules.
Product Line
PME Software
Environment
Management Console
Resolution
To prevent this error from appearing:
- In Notepad, navigate to ...\Program Files (x86)\Schneider Electric\Power Monitoring Expert\Floating License Manager\FLEXnet Publisher License Server Manager\conf\ and then open server.xml.
- Search the file for the restartRetries parameter.
- Set the parameter to 10 (restartRetries="10")
- Save and close the file.
- Restart the Flexnet Licensing and the lmadminSchneider services.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.