What is the permissible current depending on the ambient temperature on the connections of a Compact NSX NA switch disconnector installed in Prisma P enclosure?
The maximum permissible current on the connections of a Compact NSX NA switch disconnector is influenced by the ambient temperature around the switchboard. The derating for the switch disconnectors that has to be applied is equal to the values published in the attached table corresponding to the NSX circuit breaker with electronic trip units.

Schneider Electric Česká republika

Přílohy
Designing connections.pdf [174.08 KB]
What is the permissible current depending on the ambient temperature on the connections of a Compact NSX NA switch disconnector installed in Prisma P enclosure?
The maximum permissible current on the connections of a Compact NSX NA switch disconnector is influenced by the ambient temperature around the switchboard. The derating for the switch disconnectors that has to be applied is equal to the values published in the attached table corresponding to the NSX circuit breaker with electronic trip units.

Schneider Electric Česká republika

Přílohy
Designing connections.pdf [174.08 KB]
Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Zjistěte více
Řada:
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.
Your browser is out of date and has known security issues.

It also may not display all features of this website or other websites.

Please upgrade your browser to access all of the features of this website.

Latest version for Google Chrome, Mozilla Firefox or Microsoft Edgeis recommended for optimal functionality.