How to export the System Key in Power Monitoring Expert?

Issue:
When installing an Engineering Client or Secondary Server, a System Key file is required from the Primary Server. This key is typically generated during the installation of the Primary Server, however this step may have been skipped, or the file has since been misplaced. Without the System Key file, an Engineering Client or Secondary Server cannot be installed.

Product Line:
Power Monitoring Expert 8.x
Power Monitoring Expert 9.0
Power Monitoring Expert 2020
Power Monitoring Expert 2021
Power Monitoring Expert 2022
Power Monitoring Expert 2023
Power Monitoring Expert 2024

Environment:
Software Installation

Resolution:
To export the System Key after Power Monitoring Exper has been installed:

  1. On the Primary Server, navigate to the Windows Control Panel and then Programs and Features
  2. Find and select "Power Monitoring Expert" from the list
  3. Click "Change" from the top of the menu to bring up the install options menu.
  4. Select the "Export System Key" option from the menu.

Schneider Electric Česká republika

Zjistěte více
Produkt:
Zjistěte více
Produkt:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie