In EcoStruxure Operator Terminal Expert (Vijeo XD v3.0), the Transfer Button is grayed and it is not possible to download a project to my Magelis HMI
Issue
In EcoStruxure Operator Terminal Expert (Vijeo XD v3.0), the Transfer Button (located in the Buildtime Editor interface on the top menu bar) is grayed out and it is not possible to download a project to my physical Magelis HMI.
Product Line
EcoStruxure Operator Terminal Expert (Vijeo XD v3.0)
Resolution
If the Vijeo XD license is not activated, Transfer to a physical Magelis HMI will not be available (grayed out) in the Buildtime Editor interface on the top menu bar..
Run the License Manager and click on the "Task" menu. Select "Register license into my account ...". Then follow the instructions shown in the dialog box.
Once the registration procedure has been completed, delete the "Vijeo XD Trial" Activation ID.
In EcoStruxure Operator Terminal Expert (Vijeo XD v3.0), the Transfer Button (located in the Buildtime Editor interface on the top menu bar) is grayed out and it is not possible to download a project to my physical Magelis HMI.
Product Line
EcoStruxure Operator Terminal Expert (Vijeo XD v3.0)
Resolution
If the Vijeo XD license is not activated, Transfer to a physical Magelis HMI will not be available (grayed out) in the Buildtime Editor interface on the top menu bar..
Run the License Manager and click on the "Task" menu. Select "Register license into my account ...". Then follow the instructions shown in the dialog box.
Once the registration procedure has been completed, delete the "Vijeo XD Trial" Activation ID.
Publikováno pro: Schneider Electric Česká republika
Přílohy
Zjistěte více
Produkt:
Zjistěte více
Produkt:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.