Jak vám dnes můžeme pomoci?

Is it possible to operate the Altivar ATV variable speed drives with a Step-Up transformer at the output?

Altivar Process variable speed drive can be used in a Step-up solution (ATV drive + sinus filter + step-up transformer + motor). There is no special version necessary like S387 that was needed for ATV61
So we can offer ATV930/ATV950/ATV960/ATV980 with a sinus filter for step-up solutions.
Required settings for the transformer on the output:
[Motor Control Type] Ctt = U/f 5pts
[Sinus Filter Activation] OFI = Yes

For Altivar machine (ATV320, ATV340) there is no such possibility. First, Altivar machine offer is dedicated to machines that have limited power range, and second, the machines use standard voltage class. No sinus filter exists for ATV320 and ATV340

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie