OFS 3.61 doesn’t start when installed on Windows 10 64bit.
Installation occurs perfectly but when you want to run the OPC Factory Server then the message below is displayed:
“CoCreateInstance returned CO_E)SERVER_EXEC_FAILURE for server Schneider-Automation”
With OFS 3.61 the folder C:\temp must be present and on Windows 10 native this folder doesn’t exist.
To solve this issue, you must create manually this folder. With OFS 3.61 SP1, presence to this folder will be check and if necessary will be create.
In Windows 2012 R2 and Windows Server 2016 Standard have been reported similar behaviors, OFS starting and immediately stopping. C:\Temp folder was missing and creating it manually was solving the issue.
“CoCreateInstance returned CO_E)SERVER_EXEC_FAILURE for server Schneider-Automation”
With OFS 3.61 the folder C:\temp must be present and on Windows 10 native this folder doesn’t exist.
To solve this issue, you must create manually this folder. With OFS 3.61 SP1, presence to this folder will be check and if necessary will be create.
In Windows 2012 R2 and Windows Server 2016 Standard have been reported similar behaviors, OFS starting and immediately stopping. C:\Temp folder was missing and creating it manually was solving the issue.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.