Can a dynamic braking resistor be used with an ATV6xx Process Drive?
Issue:
Is it possible to use a Dynamic Braking Resistor with an ATV630 Process Drive?
Product Line:
Altivar 630, 660, 680
Environment:
All
Cause:
Application requires the use of a braking resistor
Resolution:
A dynamic braking resistor cannot be used with an ATV6xx Process Drive. There is no access to the DC bus terminals (PA+ and PC-), and there is no PB terminal.
At this point in time this is the only drive line that cannot be connected to a braking resistor. On most other drives you would normally wire a braking resistor to the PA and PB terminals.
If a braking resistor is needed, consider using an ATV9xx Process Drive instead.
Is it possible to use a Dynamic Braking Resistor with an ATV630 Process Drive?
Product Line:
Altivar 630, 660, 680
Environment:
All
Cause:
Application requires the use of a braking resistor
Resolution:
A dynamic braking resistor cannot be used with an ATV6xx Process Drive. There is no access to the DC bus terminals (PA+ and PC-), and there is no PB terminal.
At this point in time this is the only drive line that cannot be connected to a braking resistor. On most other drives you would normally wire a braking resistor to the PA and PB terminals.
If a braking resistor is needed, consider using an ATV9xx Process Drive instead.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.