Issue:
He is testing the ATV630 drive and wants to be able to easily reset the drive without a power cycle.
Product line:
Altivar Process, ATV630
Environment:
all
Cause:
n/a
Resolution:
To Reset the Altivar Process drive on the keypad using the Stop/Reset button, the drive has to be in HMI command mode. The HMI needs to be enabled from the Command and Reference menu first.
Go to Complete Settings > Command and Reference > HMI Cmd.. Change this from Disabled to Bumpless.
Now you can use the Local/Remote button to put the drive into HMI command and then the Stop/Reset button to clear the fault.
Note, only certain faults are able to be reset by input or the HMI. Check the ATV600 programming manual under each individual fault code to see if a Power Reset (power cycle) is needed to clear the fault.
He is testing the ATV630 drive and wants to be able to easily reset the drive without a power cycle.
Product line:
Altivar Process, ATV630
Environment:
all
Cause:
n/a
Resolution:
To Reset the Altivar Process drive on the keypad using the Stop/Reset button, the drive has to be in HMI command mode. The HMI needs to be enabled from the Command and Reference menu first.
Go to Complete Settings > Command and Reference > HMI Cmd.. Change this from Disabled to Bumpless.
Now you can use the Local/Remote button to put the drive into HMI command and then the Stop/Reset button to clear the fault.
Note, only certain faults are able to be reset by input or the HMI. Check the ATV600 programming manual under each individual fault code to see if a Power Reset (power cycle) is needed to clear the fault.
Publikováno pro: Schneider Electric Česká republika




Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.