Jak vám dnes můžeme pomoci?

What is the behavior of the FPI if the parameter cross-country fault detection is disabled?

  • This option is used to enable detection of "double" fault currents, i.e. 2 simultaneous phase-to-ground faults on 2 phases and at 2 different locations on the network.
  • In case of double fault on 2 different locations of the network, the 2 directions will be indicated.
  • In all cases this generates 2 phase faults. With this option the cross-country fault alarm will be set in addition to the phase faults.
Note: cross-country fault detections are only available on instance 3 of a zero sequence fault (in ammetric fault detection).
This case should not be confused with what is called "double fault" in France, which is referring to 2 faults in sequence

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie