Unity appears to freeze or lock up. How do I correct this condition?
This behaviour occurs when conditions as described below are present:
A laptop with an external screen is used. On Display Settings screen, inside the field Multiple displays the option Extends these displays is selected and main display is still the Laptop screen.
From Unity Pro application you open a window (e.g. Types Library Manager) and you send this window to the extended screen. Doing this you declare this screen as the one by default for this specific window.
Problem will occur when the extended screen is disconnected and then you open this specific window (still the Types Library Manager), the window is sent to a screen which no longer exists. Hence Unity Pro on your laptop, the main screen, is no more active (freezes).
Pressing the ESC key will close this window and so will unfreeze Unity Pro but won't solve the issue, each time you are going to open this window, the problem will occur.
Instead of pressing the ESC key use the combination of ATL + SPACE + M keys. Doing this it is possible to move the window from this virtual screen (not connected) to the main screen with the help of arrow keys such as left, right, up or down.
A laptop with an external screen is used. On Display Settings screen, inside the field Multiple displays the option Extends these displays is selected and main display is still the Laptop screen.
From Unity Pro application you open a window (e.g. Types Library Manager) and you send this window to the extended screen. Doing this you declare this screen as the one by default for this specific window.
Problem will occur when the extended screen is disconnected and then you open this specific window (still the Types Library Manager), the window is sent to a screen which no longer exists. Hence Unity Pro on your laptop, the main screen, is no more active (freezes).
Pressing the ESC key will close this window and so will unfreeze Unity Pro but won't solve the issue, each time you are going to open this window, the problem will occur.
Instead of pressing the ESC key use the combination of ATL + SPACE + M keys. Doing this it is possible to move the window from this virtual screen (not connected) to the main screen with the help of arrow keys such as left, right, up or down.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.