How to setup an Alarm Variable in EcoStruxure Operator Terminal Expert (formerly known as Vijeo XD)?

Issue:
Cannot find where in EcoStruxure Operator Terminal Expert (formerly known as Vijeo XD) to create an Alarm Variable.

Product Line:
EcoStruxure Operator Terminal Expert, Vijeo XD 3.0 or higher.

Resolution:




In order to setup an Alarm Variable in Vijeo XD, there are a few steps you need to make.

1) First create an Alarm Group by first selecting "Alarms / Events" and then press the + Alarm Group button
Selection menu
2) Create a variable to use as the Alarm Variable
3) Expand the Alarm Group and choose the type of alarm you would like to create (BOOL / LEVEL)
4) Press the +Alarm Button to add the variable that you created. (See below)
Menu

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie