Jak vám dnes můžeme pomoci?

Graphic Display terminal VW3A1111 of Altivar Variable speed drives (ATV6xx/ATV9xx) used for RESET function

The VW3A1111 Graphic Display Terminal can be used to perform a drive RESET on Altivar ATV6xx / ATV9xx drives, regardless of the configured control channel.
However, this functionality must be explicitly enabled in the drive parameters.

Parameter setting
Navigate to:
5.5 Command and Reference → Stop key Enable (PST parameter)

Default value: Yes
Available values:

No
Yes
All


Key configuration

When set to All, the drive reset function via the VW3A1111 terminal is enabled for all control channels
This allows the reset to be executed independently of the active control mode (e.g. terminals, fieldbus, HMI)


Practical implication

Without selecting All, the reset command may be restricted by the active control channel
For maintenance and troubleshooting, setting All ensures that the HMI reset is always available

Schneider Electric Česká republika

Zjistěte více

Potřebujete pomoc?

Nástroj pro výběr produktů

Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.

Získejte nabídku

Poptejte se nás online a náš lokální specialista se s vámi spojí!

Kde nakoupit?

Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.

Centrum nápovědy

Zdroje podpory pro všechny své potřeby najdete na jednom místě.