What would cause the ATV630 or ATV930 Process drives to trip out on a CFA error?
Issue:
What is the CFA fault code on the ATV630 or ATV930 Process drives?

Product Line:
ATV630 or ATV930

Environment:
All

Cause:
The monitoring function has detected an error on the digital input assigned to [CabinetCircuit A Assign].
CFA is active when the detected error duration is longer than [CabinetCircuit A Delay] FdA.

Resolution:
The fault can only appear if a cabinet input has been configured as Cabinet Circuit A error.
The stop type when the fault appears is configurable.
The acquisition time of LI is 2ms.
Probable cause:
The monitoring function has detected an error on the digital input assigned to [CabinetCircuit A Assign].
CFA is active when the detected error duration is longer than [CabinetCircuit A Delay] FdA.
Remedies:
• Check the connected device (door switch, thermal switch,…) and its wiring.
• Check the parameters CFAA (high/low assignment of the cabinet IO)

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie