Data Center Expert | Download the Essential Device Definition File (DDF) for NetBotz Rack Monitor 750
Issue:
You cannot use the Web UI password to download the essential Device Definition (DDF) file for the Rack Monitor 750 in StruxureWare Data Center Expert (DCE).
Product Line
StruxureWare Data Center Expert (DCE)
InfraStruXure Central (ISXC)
Netbotz 700 Series
-Netbotz 750 (NBRK0750)
Cause:
You must use the Root account user name and password to download the Essential Alerts Device Definition File (DDF) for the Rack Monitor 750. The Essential Alerts DDF is a secondary DDF used by DCE that defines the pre-configured alarms for which DCE will alert.
Resolution:
Use the Root account user name and password to download the DDF. The default user name is root. You set the password on first use. See the User Guide on www.apc.com for instructions to set or reset the Root password.
You cannot use the Web UI password to download the essential Device Definition (DDF) file for the Rack Monitor 750 in StruxureWare Data Center Expert (DCE).
Product Line
StruxureWare Data Center Expert (DCE)
- Basic Appliance (AP9465)
- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)
StruxureWare Central (SWC)- Standard Appliance (AP9470)
- Enterprise Appliance (AP9475)
- Virtual Appliance (AP94VMACT)
InfraStruXure Central (ISXC)
Netbotz 700 Series
-Netbotz 750 (NBRK0750)
Cause:
You must use the Root account user name and password to download the Essential Alerts Device Definition File (DDF) for the Rack Monitor 750. The Essential Alerts DDF is a secondary DDF used by DCE that defines the pre-configured alarms for which DCE will alert.
Resolution:
Use the Root account user name and password to download the DDF. The default user name is root. You set the password on first use. See the User Guide on www.apc.com for instructions to set or reset the Root password.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.