How do I add a BOOLEAN Momentary On switch in EcoStruxure Operator Terminal Expert?

Issue
How do I add a BOOLEAN Momentary On switch in EcoStruxure Operator Terminal Expert?

Product Line
Vijeo XD, EcoStruxure Operator Terminal Expert

Environment
Configuration Software in Windows

Resolution
By using a script, we can customize this behavior for any screen object:

Method 1: A script that sets a BOOL for a defined time upon button press (of a Rectangle object).

See attachment "Method 1 Script - Timed Set-Reset.png" for the sample script to do this.
The screenshot describes an Object "Rectangle 7" that on press will Set the BOOL Variable named "ResetCounter" to TRUE for 0.5seconds, then Reset the "ResetCounter" back to false after the 0.5seconds elapsed time.
Blockly


Method 2: A script that sets a BOOL to TRUE on button press, and resets the value back to FALSE on release.

See attachment "Method 2 Script - On Touch and Release.png" for the sample script to do this.
The screenshot describes an Object "Rectangle 1" that on press will SET the BOOL Variable named "MyBOOL" to TRUE, and upon releasing touch of that Rectangle will RESET the value of MyBOOL to FALSE.
Blocky 2

Note: A switch with a built-in "Momentary On" functionality, will be included in the future version - EcoStruxure Operator Terminal Expert v3.2. The release date of this software has not yet been announced.

Schneider Electric Česká republika

Zjistěte více

Zjistěte více

Potřebujete pomoc?

Nástroj pro výběr produktů

Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.

Získejte nabídku

Poptejte se nás online a náš lokální specialista se s vámi spojí!

Kde nakoupit?

Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.

Centrum nápovědy

Zdroje podpory pro všechny své potřeby najdete na jednom místě.