NetBotz v5 | Configure Email Notifications
Issue:
Process for configuring email notifications on a NetBotz version 5 appliance.
Product Line:
NetBotz 750
Environment:
NetBotz v5 (all firmware versions)
Resolution:
Configuring the Email Server
Configuring an Email Notification
Configuring the Email Server
1) Log into the web interface using administrator credentials.
2) In the upper-right click on Settings and then select System.
3) Select SMTP Server in the left pane.
4) Fill in the necessary SMTP Server details, including any authentication settings that may be required by your SMTP server setup.
5) Select Send Test Email.
6) Fill in the email address to send the test email to.
7) Select Send and then check the email account for the test email.
Configuring an Email Notification
1) In the upper-right click on Settings and then select System.
2) Click on the add button.
3) Type in a name for the notification policy.
4) Type in the email addresses that should receive the notification, using commas to separate multiple addresses.
5) Select the severities that should generate the email notification.
6) Select the desired Units and Time format under the Regional settings section.
7) Select OK to save the notification policy.
Process for configuring email notifications on a NetBotz version 5 appliance.
Product Line:
NetBotz 750
Environment:
NetBotz v5 (all firmware versions)
Resolution:
Configuring the Email Server
Configuring an Email Notification
Configuring the Email Server
1) Log into the web interface using administrator credentials.
2) In the upper-right click on Settings and then select System.
3) Select SMTP Server in the left pane.
4) Fill in the necessary SMTP Server details, including any authentication settings that may be required by your SMTP server setup.
5) Select Send Test Email.
6) Fill in the email address to send the test email to.
7) Select Send and then check the email account for the test email.
Configuring an Email Notification
1) In the upper-right click on Settings and then select System.
2) Click on the add button.
3) Type in a name for the notification policy.
4) Type in the email addresses that should receive the notification, using commas to separate multiple addresses.
5) Select the severities that should generate the email notification.
6) Select the desired Units and Time format under the Regional settings section.
7) Select OK to save the notification policy.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.