Issue:
2 Wire Control on ATS22 S6
Product Line:
ATS22, Altistart 22
Environment:
All
Cause:
NA
Resolution:
The S6 requires constant 230VAC to terminals CL1 (hot) and CL2 (neutral).
Connect a jumper from Terminal LI1 to LI2.
Close a dry contact between Terminals 24V and LI2 for a run Forward. Open this connection for a freewheel stop.
For a controlled stop, do not jumper LI1 to LI2. Instead, jumper 24V to LI1 and wire dry contact between 24V and LI2. Program SEt - dEC = ramp down time.
Reference the User manual # BBV51330 or the Quick Start Annex # S1A14738 for more information.
2 Wire Control on ATS22 S6
Product Line:
ATS22, Altistart 22
Environment:
All
Cause:
NA
Resolution:
The S6 requires constant 230VAC to terminals CL1 (hot) and CL2 (neutral).
Connect a jumper from Terminal LI1 to LI2.
Close a dry contact between Terminals 24V and LI2 for a run Forward. Open this connection for a freewheel stop.
For a controlled stop, do not jumper LI1 to LI2. Instead, jumper 24V to LI1 and wire dry contact between 24V and LI2. Program SEt - dEC = ramp down time.
Reference the User manual # BBV51330 or the Quick Start Annex # S1A14738 for more information.
Publikováno pro: Schneider Electric Česká republika

