How is the ATV212 set for RUN/STOP on the terminals and speed reference from the keypad UP/DOWN arrows?

Article available in these languages: Španělština

Issue:
How do you change parameters on the ATV212  for RUN/STOP on the terminals and UP/DOWN arrows for the speed reference.

Product Line:
Altivar Machines, Altivar 212

Resolution:

Press Mode until you see AUF
Scroll to CNOD, enter 0 for terminals Start/Stop control.
Scroll to FNOD, enter 3 for keypad UP/DOWN arrow button speed control.

If this article does not answer your question, check out our FAQ database that has answers to more commonly asked questions:

Frequently Asked Questions - Schneider Electric (se.com)

If this FAQ did not solve your issue, you can call us at 1-888-778-2733 Option 2 and then 4 or e-mail us at drive.products.support@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie