How can I perform a factory reset on my S-flex drive system?
Issue:
Reset S-flex to factory settings.
Product line:
S-flex enclosed systems (SFD212XXXXX)
Environment:
All models, All serial numbers.
Cause:
The factory reset process for the open style ATV212 drive and enclosed S-flex systems are very different. It is important that the correct process be followed.
Resolution:
Make sure the S-flex system does not have a command to run.
Press Mode (ESC if using the full graphic keypad)
Scroll down until TYP (Parameter reset) is found and press Enter.
Press the up arrow until the number on the right is 8 (recall parameters) and then press Enter. The drive will reboot and will be returned to factory control settings for the S-flex system.
Reset S-flex to factory settings.
Product line:
S-flex enclosed systems (SFD212XXXXX)
Environment:
All models, All serial numbers.
Cause:
The factory reset process for the open style ATV212 drive and enclosed S-flex systems are very different. It is important that the correct process be followed.
Resolution:
Make sure the S-flex system does not have a command to run.
Press Mode (ESC if using the full graphic keypad)
Scroll down until TYP (Parameter reset) is found and press Enter.
Press the up arrow until the number on the right is 8 (recall parameters) and then press Enter. The drive will reboot and will be returned to factory control settings for the S-flex system.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.