Jak vám dnes můžeme pomoci?
How can I change the relay status from NO to NC on the Altivar Process Drives?
Issue:
They need to change the function of the output relay from Normally Open contact to a Normally Closed contact.
Product line:
Altivar Process, ATV600 ATV900
Environment:
all
Cause:
The Altivar Process drives come with only R1 having a normally open and normally closed contact. R2, R3 and the extended IO Card relays are all Normally Open only.
Resolution:
Under the Relay configuration menu (i.e. R2 Configuration > go to R2 Active at. The factory setting is 1 (closed). Change this value to 0 for active when open to invert the relay output signal.
NOTE: Operating State Fault (FLT) cannot be assigned to 0. If an additional NC contact is needed for Fault indication, add an external control relay with the additional contacts.
They need to change the function of the output relay from Normally Open contact to a Normally Closed contact.
Product line:
Altivar Process, ATV600 ATV900
Environment:
all
Cause:
The Altivar Process drives come with only R1 having a normally open and normally closed contact. R2, R3 and the extended IO Card relays are all Normally Open only.
Resolution:
Under the Relay configuration menu (i.e. R2 Configuration > go to R2 Active at. The factory setting is 1 (closed). Change this value to 0 for active when open to invert the relay output signal.
NOTE: Operating State Fault (FLT) cannot be assigned to 0. If an additional NC contact is needed for Fault indication, add an external control relay with the additional contacts.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.