Issue:
Change the default display for when the drive is powered on to show output frequency.
Product Line:
Altivar Machines, Altivar 320
Environment:
All models and serial numbers
Cause:
Default display is Reference Frequency
Resolution:
Go to Non (1.2 Monitoring) menu, select rFr (output frequency), and press and hold ENT for more than 2 seconds. Display will flash to indicate the change had been made.
To dispaly amperage: Go to NON > select NNO > LCr, ENT for more than 2 seconds