Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
How do I configure the ATV930 Process Drive for Positioning by Sensor?
Issue:
ATV930 Positioning by Sensor

Product Line:
Altivar Process Drive

Environment:
ALL

Cause:
Wiring and configuration

Resolution:
ATV900 - Positioning by Sensor

Complete Settings > Generic Functions > Positioning By Sensor
DI1 = Fwd
DI2 = Rev
DI3 = SAF (Stop Fwd)
DI4 = SAR (Stop Rev)
DI5 = DAF (Slow Fwd)
DI6 = SAR (Slow Rev)
**MSTP = Memory Stop = NO (this step is Very Important)
Command and Reference
Ref 1 = AI1
LSP = SLOW Fwd/Rev
(LSP has to be lower than Ref 1)

Note:
Does not work with JOG or PSS
Enable DI1, runs at FR1, Enable DAF drops to LSP, Enable DAF Stops/RDY
Enable DI2, runs at FR1, Enable SAR, drops to LSP, Enable SAF Stops/RDY

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie