Naše značky

Impact-Company-Logo-English Black-01-177x54

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
Power Monitoring Expert - Power Quality Report is missing *Exceeds Tolerance indicator
Issue
The power quality report no longer indicates which events have exceeded tolerance and no longer tags them with "*Exceeds Tolerance"

Product Line
Power Monitoring Expert (PME) 8.2
Power Monitoring Expert (PME) 9.0

Cause
This indicator was removed in PME8.2 due to a UX decision.

Resolution
This has only been tested on a PME9.0 system.  It has not been tested on PME 8.2.

1) Navigate to the folder \Power Monitoring Expert\web\ReportDepot\ION Reports\ION Report Packs\StandardPowerQualityReports\
2) Create backup copy of the "Power Quality Report.rdlc".
3) Overwrite the "Power Quality Report.rdlc" with the new "Power Quality Report.rdlc" attached to this KB

This new rdlc has been modified to show "*Exceeds Tolerance".  This text has been hardcoded in English and will not translate into other languages.


Schneider Electric Česká republika

Přílohy
Hotfix_100454_ExceedsTolerancePQReport.zip [15.06 KB]
Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie