PME 9.0 - Web Application - Diagrams - "There was a problem processing you request"
Power Monitoring Expert 9.0
Enviroment
Digramas/DatalogViewer - Web Application
Issue
When attempting to open a diagram in Web Application the system gives an error: "There was a problem processing you request"
Issue 1
Error opening a Diagram
It can be another IonName.[Language].resx file as well.
Cause
This was probably an upgraded system where the diagram link was referencing an existing resx file that in the current version has been renamed or does not exist anymore.
Resolution
Navigate to C:\Program Files (x86)\Schneider Electric\Power Monitoring Expert\system\etc
Search for IONNames.[LANGUAGE_DESIRED].resx
Make a copy of it
Always keep the original in the folder
Rename the copy to match the file name that the error is claiming that could not be found
IIS reset and refresh the Web Page
Issue 2
Error opening a Datalog Viewer
Error in: https://wasg00115/ion/Historical/DisplayLogs.aspx?queryId=8a2a27f8-a578-43bf-9b3c-cb49a19cdef6&dgm=x-pml:/diagrams/ud/default/PM820_FAC-4WYE_V1.1.5/PM820_FAC-4WYE_V1.1.5-rev.dgm&node=HUB-L4.PM-MSB-INC&logServerName=QUERYSERVER.TNETVMPME9&logServerHandle=327952&isEventLog=
Error Message: An error occurred in GetConnectionStringFromQueryServer calling method lsSetupObject.GetConnectionString while attempting to access Query Server [QUERYSERVER.OLD_SERVER_NAME] with handle [327952].<br>With moniker: pmlitem:QUERYSERVER.TNETVMPME9:pmlnew:PMLQueryServer.IONModuleInfo:<br><br>The Query Server may not be running.<br>
Stack Trace: at WebReach.Historical.MapPegQueryToSQL.GetConnectionStringFromQueryServer(String lsSoftwareNode, String lsHandle)
at WebReach.Historical.MapPegQueryToSQL.Execute(Int32 numRecordsToGet, String dgm, String node, String queryId, String isEventLog, String logServerName, String logServerHandle, String whereClause)
at WebReach.Historical.MapPegQueryToSQL.Execute(Int32 numRecordsToGet, NameValueCollection args)
at WebReach.Historical.DisplayLogs.Page_Load(Object sender, EventArgs e)
at System.Web.Util.CalliEventHandlerDelegateProxy.Callback(Object sender, EventArgs e)
at System.Web.UI.Control.OnLoad(EventArgs e)
at System.Web.UI.Control.LoadRecursive()
at System.Web.UI.Page.ProcessRequestMain(Boolean includeStagesBeforeAsyncPoint, Boolean includeStagesAfterAsyncPoint)
Cause
This issue happens when the device icons are pasted in custom diagrams and query server is not properly set in the custom vista diagram pages. When check the url when a meter template is opened you can see the query server name weater it is properly passe or not -
https://wasg00115/ion/default.aspx?dgm=x-pml:/diagrams/ud/default/PM820_FAC-4WYE_V1.1.5/PM820_FAC-4WYE_V1.1.5-rev.dgm&node=HUB-L4.PM-MSB-INC&logServerName=QUERYSERVER.OLD_SERVER_NAME&logServerHandle=327952
in this case the URL is pointing to wrong query server.
Resolution
Open the diagram in Vista and right click on page > Properties > Query server > Select 'custom query server' > click on "Edit Link" button > and select the local PME query server.
Restat 'ION Application Modules Core Services Host' service and refresh the browser
Publikováno pro: Schneider Electric Česká republika
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.