What are the default IP addresses on the M241/M251 controllers?

Depending on the Software and Firmware version, the default IP addresses are:

With SoMachine and Machine Expert V1.1:

  • M241 Embedded Ethernet: 10.10.x.x
  • M241 TM4ES4: 11.11.x.x
  • M251 Eth1: 11.11.x.x
  • M251 Eth2: 10.10.x.x

The default subnet mask is Default Class A Subnet Mask of 255.0.0.0.


From Machine Expert V1.2:

  • M241 Embedded Ethernet: 10.10.x.x
  • M241 TM4ES4: 10.11.x.x
  • M251 Eth1: 10.11.x.x
  • M251 Eth2: 10.10.x.x

The default subnet mask is Default Class B Subnet Mask of 255.255.0.0.

The last 2 fields in the default IP address are composed of the decimal equivalent of the last 2 hexadecimal bytes of the MAC address of the port.
The MAC address of the port can be retrieved on the label placed on the front side of the controller.

NOTE: A MAC address is always written in hexadecimal format and an IP address in decimal format. Convert the MAC address to decimal format.
Example: If the MAC address is 00.80.F4.01.80.F2, the default IP address is x.x.128.242.

NOTE: To take into account the new IP address after the download of a project, reboot the controller by doing a power cycle.