What is the switching power of Altivar process relay outputs?
This information can be found on product datasheet on web.
Max switching power for AC load is:
2A at 250V AC providing that the load is resistive or slightly inductive with either cos phi 0.4 or better or time constant L/R of 7ms or lower.
Max switching power for DC load is:
2A at 30V DC providing that the load is resistive or slightly inductive with either cos phi 0.4 or better or time constant L/R of 7ms or lower.
Max switching power for AC load is:
2A at 250V AC providing that the load is resistive or slightly inductive with either cos phi 0.4 or better or time constant L/R of 7ms or lower.
Max switching power for DC load is:
2A at 30V DC providing that the load is resistive or slightly inductive with either cos phi 0.4 or better or time constant L/R of 7ms or lower.