Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
Why my PowerTag Sensors cannot communicate with SmartLink SIB / SID ?
If you have checked the basic commissioning steps (Smartlink powered on, pairing, communication periods, channel attribution) you can refer below.

This issue can occur for SmartLink SI D / SI B with old firmware revision when they are used in environment with high density wireless traffic (intensive RF environment). In this case, you need to replace your SmartLink SIB / SI D by a PowerTagLink A9XMWD20 or A9XMWD100.

Switch OFF / ON the wireless devices to commute the wireless device in "waiting for pairing" status and launch the wireless discovery on the gateway to pair them.
If you have not the possibility to switch OFF / ON you wireless devices (case of powertag associated to critical load) please contact your Schneider Electric technical support.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie