Hierarchy Manager Fails to Upload Records
Issue
When changing tabs in Hierarchy Manager, the system tries to upload records. However, after a few minutes, it fails and shows the following message:

Loading records...
Failed to load data from the server. Please try again.
Product Line
Power Monitoring Expert 9.0
Environment
Hierarchy Manager
Cause
By default, the hierarchy manager has to upload records within 2 minutes. If it doesn't manage to upload within this time, it will fail.
Resolution
Change the Javascript file for HierarchyManager to increase the timeout. The file is:
...\Power Monitoring Expert\applications\HierarchyManager\Scripts\HierarchyManager\data.nodemodel.js
Find the following code snippet:
$.ajax({
type: "GET",
url: baseUrl,
timeout: 2*60*1000, // 2 minutes. Some hierarchy pages can take a long time to generate.
data: { nodeQuery: JSON.stringify(nodeQuery) },
dataType: "json",
success: onSuccess,
error: onError,
page: page
});
Change the timeout to 4*60*1000. This increases the timeout to 4 minutes.
*Note: This solution does not apply to versions of PME after PME 9.0
When changing tabs in Hierarchy Manager, the system tries to upload records. However, after a few minutes, it fails and shows the following message:
Loading records...
Failed to load data from the server. Please try again.
Product Line
Power Monitoring Expert 9.0
Environment
Hierarchy Manager
Cause
By default, the hierarchy manager has to upload records within 2 minutes. If it doesn't manage to upload within this time, it will fail.
Resolution
Change the Javascript file for HierarchyManager to increase the timeout. The file is:
...\Power Monitoring Expert\applications\HierarchyManager\Scripts\HierarchyManager\data.nodemodel.js
Find the following code snippet:
$.ajax({
type: "GET",
url: baseUrl,
timeout: 2*60*1000, // 2 minutes. Some hierarchy pages can take a long time to generate.
data: { nodeQuery: JSON.stringify(nodeQuery) },
dataType: "json",
success: onSuccess,
error: onError,
page: page
});
Change the timeout to 4*60*1000. This increases the timeout to 4 minutes.
*Note: This solution does not apply to versions of PME after PME 9.0
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.