How to change PME 9.0 system from standalone to distributed architecture without changing application servers using the CM Tool?
Issue
Configuration Manager Toolversion 9.0 does not natively support upgrades or migrations to different architectures.
Product Line
Power Monitoring Expert 9.0
CM Tool 9.0
Environment
Power Monitoring Expert (PME) 9.0 Standalone to Distributed
Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*
In order to migrate from Standalone to Distributed Configuration in PME 9.0 using CM Tool, please follow these steps:
Configuration Manager Toolversion 9.0 does not natively support upgrades or migrations to different architectures.
Product Line
Power Monitoring Expert 9.0
CM Tool 9.0
Environment
Power Monitoring Expert (PME) 9.0 Standalone to Distributed
Resolution
*Warning: Irreparable database damage can occur. This procedure should only be performed by users familiar with SQL Server Management Studio. Databases should be backed up prior to performing this procedure.*
In order to migrate from Standalone to Distributed Configuration in PME 9.0 using CM Tool, please follow these steps:
- Run the CM Tool 9.0 to save archive of PME system, including the database (just in case, also take separate backup of the database and config folder in case something goes wrong with CM Tool archive)
- Uninstall PME from the Windows Control Panel > Programs and Features
- Proceed with step 1 on the attached document in order to install PME 9.0 Distributed on the Application server.
Publikováno pro: Schneider Electric Česká republika
Přílohy
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.