PSO Notification Settings and Notification History popup does not open
Where
Product Line
Power SCADA Operation 9.x
Environment
Power SCADA Operation 9.x
Cause
Known issue with PSO 9.0 CU2. Will be fixed in CU3
Resolution
*Warning: Take backups of any files prior to modifying them. Ensure the backups are in a location that will not be overwritten (i.e. the Desktop).
IMPORTANT: Solution is only applicable to Cumulative Update 2, do not apply if you are not updated to this version.
Find & Edit the "PLSNotification.ci" inside your PLS_Inlcudes project. Preferably using your Cicode Editor from your PSO Studio IDE.
Use the "Find Function" feature to find the following function:
```
LaunchNotificationSettings()
```
Inside this function there is a method/ subroutine called
```
DllClassCallMethod(m_oNotificationServiceInstance, "LaunchSettings", sDataPath, sIPs, sUserName, sLanguage);
```
Comment out the "sLangauge" argument & Re-terminate the statement. Like this.
```
DllClassCallMethod(m_oNotificationServiceInstance, "LaunchSettings", sDataPath, sIPs, sUserName);//, sLanguage);
```
Do the same for this FUNCTION:
LaunchNotificationHistory(STRING sFilter, STRING sClusterName = "")
Replace
```
DllClassCallMethod(m_oNotificationServiceInstance, "LaunchResults", sDataPath, sIPs, sClusterName, sFilter, sLanguage);
```
With
```
DllClassCallMethod(m_oNotificationServiceInstance, "LaunchResults", sDataPath, sIPs, sClusterName, sFilter);//, sLanguage);
```
Save the LaunchNotificationSettings function.
Update Pages in citect gfx builder.
Always "Pack" databases on your projects
Recompile your project. Remember to perform a full recompile, not an incremental one.
Always run "Computer Setup Wizard".
Run your project.
Publikováno pro: Schneider Electric Česká republika
Zjistěte více
Řada:
Zjistěte více
Řada:
Potřebujete pomoc?
Nástroj pro výběr produktů
Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.
Získejte nabídku
Poptejte se nás online a náš lokální specialista se s vámi spojí!
Kde nakoupit?
Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.
Centrum nápovědy
Zdroje podpory pro všechny své potřeby najdete na jednom místě.