Naše značky

Vítejte na internetových stránkách společnosti Schneider Electric

Vítejte na našich internetových stránkách.
		
Jak vám dnes můžeme pomoci?
Can the M580 communicate with an Allen Bradley PLC and pull tag information?
Issue
Allen Bradley communications

Product Line
Modicon M580

Environment
Control Expert
Unity Pro

Resolution
The M580 can send an explicit Ethernet IP message to a Contrologix PLC as long as it is sent to an Ethernet/IP object that supports being read or written.
Note: You will need to talk to the Contrologix PLC support on what Ethernet/IP objects a remote Ethernet/IP Scanner device can read or write.

Contrologix PLCs can read and write each others Tag database via Ethernet/IP using the proprietary Client Server Protocol ("CSP") protocol, with embedded PCCC  (Programmable Controller Communication Commands) commands. This Ethernet/IP (CSP/PCCC) protocol is a proprietary implementation of Ethernet/IP and Schneider Electric does not have access to it.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie