PME 8.2 distributed install fails on 'Configure SQL Server' and 'Verify Databases' steps

Issue
When installing PME 8.2 distributed, the 'Configure SQL Server' step is not successful and the installer stops at 'Verify Databases'. The installation log includes an error such as "Could not deploy package. Missing values for the following SqlCmd variables:LogFilePath".

Verify databases error

Product Line
Power Monitoring Expert 8.2

Environment
Software Install

Cause
During the Database Files Destination step, the destination folder selected was at the root of a drive (for example, C:\ as shown below). This is a SQL restriction as SQL data and log files cannot be placed in the root of a drive, because of the way permissions work with regards to the root of the drive compared to its subfolders.

Database files destination

Resolution
Specify at least one subfolder as the location for the database files.

Database files destination with subfolder

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie