​​​​​​​The Web Designer project 'LookUp Variable' table does not show any variables.

Issue
The Web Designer project 'LookUp Table' does not show any variables.

Product Line
BMXNOE0110

Environment
Web Designer

Resolution
If you try to open the Lookup Table, a blank table will get returned.
i2



If you try to open the 'Namespace', the following error gets returned.
I3



The issue is due to the 'Namespace' file  being missing or corrupted in the project.  This is causes the variables not getting populated in the 'LookUp Variable' table..

The following steps can be used to resolve the issue
  • Backup the project.
  • Navigate to the folder named ‘C:\Users\username\Documents\Schneider Electric\Web Designer\projects\Prueba_PPPN_RB\BMX NOE 0110-NOE_PPPN’.
  • Delete the file named ‘Namespace.dat’.
I4


  • Open the ‘Device ’ table
  • Click ‘Export to CSV’ option
  • Save the file.
I5



  • Import the variables again using ‘Import From CSV’ option in the same page
(Variables will be imported again and namespace file will be created newly in the project folder.)
I67



Now We can able to view the variables when we open the any one of the graphics page.

I68

Schneider Electric Česká republika

Zjistěte více

Produkt:

Řada:

Zjistěte více

Produkt:

Řada:

Potřebujete pomoc?

Nástroj pro výběr produktů

Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.

Získejte nabídku

Poptejte se nás online a náš lokální specialista se s vámi spojí!

Kde nakoupit?

Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.

Centrum nápovědy

Zdroje podpory pro všechny své potřeby najdete na jednom místě.