How to check Heat Tag and communication gateways on Smart solutions tab in NL 4.9.3 version of Ecodial .

Steps to check Heat Tag and communication gateways in Smart solution tab in Ecodial :
STEP-1 Launch Ecodial 4.9.3 NL version of Ecodial
STEP-2 Create a network with 50, 100 and 200A load.
STEP-3  Run the calculation
STEP-4  GO to Smart solution tab
STEP-5 Under fire prevention tab  select the required circuit breaker & switchboards to be protected
STEP-6 Run Smart solution by clicking “ SMART SOLUTION” TAB
STEP-7 Smart solution results will appear as below :
Under  “Electrical Fire prevention” solutions check there exists heat tags and communication gateways for the respective switchboards which is  required  for fire prevention.
STEP -8 Follow the instruction which application is suggesting in “ Electrical  Fire prevention “tab.
STEP-9  After following the instruction by adding add on RCD go to “ smart solution tab “ and again “ Run smart solution”
STEP10 – Network will charge out “ Heat  tag solution and communication gateways “ for respective circuit breakers and switchboard as below:



Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie