What is the firmware password to be used on EcoStruxure Automation Device Maintenance to update Modicon M340/M580 modules?

The EcoStruxure Automation Device Maintenance can be used to update the firmware of Modicon M340 / Modicon M580 CPUs and x80 Modules using the .ldx files. In this case, the EcoStruxure Automation Device Maintenance requires a Firmware Password.

  • If the application has no password: enter the firmware password (default or configured).
  • If the application has a password: enter both the application password and the firmware password (default or configured)
  • If there is no application in the controller, enter the firmware password (default or configured).

The default firmware password is fwdownload

Image1

Note: pictures from EADM 3.4


Default credentials used only for this Modicon M580 migration firmware V3.99:

  • Device User Name: loader
  • Devicepassword: fwdownload