Where must the wiring kit be connected in PrismaSeT Active?

You can connect the wiring kit upstream or downstream. Today, 90% of wiring kits connections are downstream.

The purpose of the wiring kit is to make sure that the wireless panel server is correctly connected with the right protection.
image.png

If you need to connect the wiring kit upstream, we highly recommend that you use an additional protection that can be opened during maintenance (without cutting off the power).

If you are looking for further information regarding the steps to follow when installing the wiring kit, watch this video:
https://www.youtube.com/watch?v=Du8xGHIu9M4

You can also access this instruction sheet:
https://download.schneider-electric.com/files?p_enDocType=Instruction+sheet&p_File_Name=NNZ50846-01.pdf&p_Doc_Ref=NNZ50846

Schneider Electric Česká republika

Potřebujete pomoc?

Potřebujete pomoc?

Nástroj pro výběr produktů

Nástroj pro výběr produktů

Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.

Získejte nabídku

Získejte nabídku

Poptejte se nás online a náš lokální specialista se s vámi spojí!

Kde nakoupit?

Kde nakoupit?

Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.

Centrum nápovědy

Centrum nápovědy

Zdroje podpory pro všechny své potřeby najdete na jednom místě.

  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie