How does one connect an HMI to Modicon M172 or M172 HVAC PLC for Modbus Serial communication?

Issue
How does one connect an HMI to Modicon M171 or M172 HVAC PLC for Modbus Serial communication?
What are the part numbers for the connectors on these PLCs?

Product Line
Modicon M171, M172 HVAC PLCs
EcoStruxure Machine Expert HVAC

Environment
Connectors for Serial communications

Resolution
The Serial connectors on Modicon M171 and M172 require a terminal block that have screw-type connectors for bare wire.
These kits are sold separately and are specific to the number of I/O pins on the corresponding model of PLC:

For the 14 I/O M171 or M172 model:
Part Number: TM171ASCTB14

For the 27I/O M171 or M172 model:
Part Number: TM171ASCTB27

The connectors attach to this port on the PLC:
physical connection

In order to connect an HMI, you would obtain the Serial Connector pinout diagram from the specific HMI's Hardware Manual, then wire the connectors accordingly.

See this example with the HMISTO715:
On the HMISTO715, the pinout is as follows:
pinout

So a cable with an RJ45 connector would have to be manually spliced from:

HMI                         M171/M172
4 D1  -----------------   “+”
5 D0 ------------------   “-“
8 SG ------------------   “GS”

If this FAQ did not solve your issue, you can chat with us at chat with us or e-mail us at customer.services@se.com to create a case with our Technical Support Team.

If you are not located in North America, please contact your local Customer Care Center for assistance:

Support | Schneider Electric Global (se.com)

Schneider Electric Česká republika

Zjistěte více

Zjistěte více

Potřebujete pomoc?

Nástroj pro výběr produktů

Rychle a snadno vyhledávejte správné produkty a příslušenství pro vaše aplikace.

Získejte nabídku

Poptejte se nás online a náš lokální specialista se s vámi spojí!

Kde nakoupit?

Jednoduše najděte nejbližšího distributora výrobků Schneider Electric ve vašem okolí.

Centrum nápovědy

Zdroje podpory pro všechny své potřeby najdete na jednom místě.