Jak vám dnes můžeme pomoci?

Why Link150 Firmware Upgrade Fail with the Upgrade Tool V3.0 ?

Issue

Few of the EGX150 units when upgraded using the upgrade tool, fail to upgrade and cause the device to be in boot mode.


Environment
EGX150 when firmware upgraded from 5.0.24 version to 5.1.22 version using, 3.0 version of upgrade tool.


Cause
The mass upgrade tool is not stable to support the upgrade from very old version to the latest versions.


Resolution

Prefer the upgrade of the Link150 through Web Pages.

The Upgrade Tool was removed from se.com. Please do not share the tool for the moment.

A fix will be developed for the tool and will be available again with the package firmware on se.com.

Schneider Electric Česká republika

Zjistěte více
Produkt:
Zjistěte více
Produkt:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie