How to deactivate the User Rights only for the Web Visualization on M241/251 and M262 controllers?
As from EcoStruxure Machine Expert V2.0, it is possible to deactivate User Rights for the Web Visu only on M241/251 and M262 controllers.
That means User Rights remain active for other services.
To do it, User must create the empty file WebVisuNoLogin.cfg into the folder /usr/Visu and reboot the controller.
After this action, no password is required to connect to the web visualization.
WebVisuNoLogin.cfg file can be downloaded to the controller through FTP Server connection or from EcoStruxure Machine Expert (MyController >> Files tab).
Through FTP Server connection:
From EcoStruxure Machine Expert:
Important:
Since Machine Expert V2.3, due to the new implementation of the User Management in the Visualization Manager, it is needed to Convert it to Legacy implementation to continue using this solution. By default, the implementation mode is set to Runtime based.