Jak vám dnes můžeme pomoci?

EcoStruxure Process Expert [2020R2]: How to resolve the issue - "OFS Product with license not Activated.Server is Stopped"

This documents helps the user to overcome the below issue which happens frequently and eventually impacts the runtime of citect Scada.

Text

As a general practice,user tries to reinstall OFS server which helps to solve the issue temporarily.Later, it was found the issue is happening because the lm admin fails to fetch the license.After restarting the lm admin services,issue gets resolved temporarily.

It was understood from the logs that the communication was getting lost to lmgrd ( a core component of the licensing) due to which FLM (supervision component) is getting effected. This happens when there is unstable power which makes the system to enter into "sleep mode".

It is suggested to maintain a stable power supply to the system. Sometimes that is not possible at site. At such instances, its advised to go with the settings as mentioned below which will help to solve this issue which happens due to unstable power.

1. Open Network and Sharing Center
2. Select the change adapter settings
3. Right click on the network adapter and select 'Properties'
4. Select the 'Configure...' button
5. Select the 'Power Management' tab
6. Uncheck 'Allow the computer to turn off this device to save power'
7. Restart the vendor daemon

The screenshot below shown the checkbox which needs to be unchecked.
text-2

  1. Open Services (services.msc)
  2. Right click on FlexNet License Server Manager and select Properties
  3. Click on the Recovery tab
  4. Set the First, Second, and Subsequent failures to Restart the Service
  5. Set Reset fail count after to 1 days
  6. Set Restart service after to 0 minutes
The screenshot below shows the services settings

text-3


This issue was observed in EPE 2020R2 with FLM 2.6 version. However, it is applicable to all of the EPE and FLM versions.

Schneider Electric Česká republika

Zjistěte více
Řada:
Zjistěte více
Řada:
  • Dokumentace k produktům
  • Software ke stažení
  • Nástroj pro výběr produktů
  • Hledání náhrady za produkty
  • Centrum nápovědy a kontakty
  • Najít naše pobočky
  • Získejte nabídku
  • Kde koupit
  • Komunita Schneider Electric
  • Kariéra
  • Profil společnosti
  • Nahlásit nevhodné chování
  • Přístupnost
  • Newsroom
  • Investoři
  • EcoStruxure
  • Vyhledávání pracovních míst
  • Blog
  • Všeobecné obchodní podmínky
  • Zásady ochrany osobních údajů
  • Oznámení o souborech cookie
  • Podmínky použití
  • Změnit nastavení souborů cookie