What would cause the motor protection dv/dt output filter on the ATV630 Drive to overheat or smell hot when running above 60hz?
Issue:
dv/dt output filter is overheating or smelling hot when the drive is running above 60hz.
Product Line:
ATV all series with a dv/dt output filter
Environment:
All
Cause:
Running the motor speed above the dv/dt filters rated speed.
Resolution:
You need to check with the dv/dt motor protection manufacture to see what the rated speed specs are. If the rated speed is 0 -60hz then you can not run the motor above the rated 60hz speed.