How to upload and convert a Modicon Micro 110CPU612xx Modsoft application to Unity.

Use the following steps to upload the application using Modsoft:

  • Start Modsoft.
  • Click on Transfer
  • Select 'PLC to File'.
  • Select 'New Program'.

image.png

  • Type in a filename.
  • Hit ENTER

image.png

  • Type in a location for saving the application or just use the default location.
  • Hit ENTER

image.png

  • Type in the Modbus address.
  • Hit Enter.

image.png


  • Select the Modbus I

image.png


  • Select RTU for the mode.

image.png


  • Select Even for the parity

image.png


  • Select the Stop Bit.

image.png


  • Select the baud rate.

image.png


  • Select the appropriate COM port on the PC.
    • Wait for the upload to finish.
    • Save the changes.

    image.png


    • Start
    • Open the application with Unity using the 'Modsoft projects' selection.
    • Save the Unity application.

    image.png

    image.png

    • Select the PLC type to convert to:
    • Click on OK.

    image.png

    Schneider Electric Česká republika

    Zjistěte více
    Řada:
    Zjistěte více
    Řada:
    • Dokumentace k produktům
    • Software ke stažení
    • Nástroj pro výběr produktů
    • Hledání náhrady za produkty
    • Centrum nápovědy a kontakty
    • Najít naše pobočky
    • Získejte nabídku
    • Kde koupit
    • Komunita Schneider Electric
    • Kariéra
    • Profil společnosti
    • Nahlásit nevhodné chování
    • Přístupnost
    • Newsroom
    • Investoři
    • EcoStruxure
    • Vyhledávání pracovních míst
    • Blog
    • Všeobecné obchodní podmínky
    • Zásady ochrany osobních údajů
    • Oznámení o souborech cookie
    • Podmínky použití
    • Změnit nastavení souborů cookie